SC-MP640.12

Product NamesModelsDetailed parameters
KNX Bus Power SupplySC-MP640.12                      Input Voltage:200~240 VAC,50/60Hz
                      KNX Bus Output:with reactor,30VDC +1/-2V,640mA Max
                      1st Channel Auxiliary Output:30VDC , 500mA Max
                      2nd Channel Auxiliary Output:12VDC,  300mA Max
                      Maintenance Time After Power Outage:>200ms
                       Operating Temperature:-5°~+45°C 
                      Storage Temperature:-25°~+55°C 
                      Transporttation Temperature:-25°~+70°C 
                      Relative Humidity:Max 90% 
                      Shell Material:PA66
                      Size【L x W x H】:144mm x 90mm x 64mm
                      Installation Method:35mm Din rail installation

Function Description:
1. For KNX power supply only
2. The 1st and the 2nd channel auxiliary output are using the same yellow status LED. When the power supply is steady the LED lights on.When the power supply is overloading the LED flashes.
3. When the KNX bus output is over the standard 640mA the red LED lights on. And if the KNX bus output is over 900mA the red LED flashes and the output should be cut off automatically. Please press the "reset" button to restart.


TOP